NI5-G12-Y1X is a TURCK inductive sensor with a NAMUR output to EN 60947-5-6, approved for ATEX zones 0 and 20. It connects to an intrinsically safe isolating amplifier.
- Switching distance: 5 mm, non-flush mounting; correction factors steel 1, stainless steel 0.7, brass 0.4, aluminium 0.3
- Output: NAMUR, 2-wire, ≥ 2.1 mA not actuated / ≤ 1.2 mA actuated, switching frequency 2 kHz
- Supply: nom. 8.2 VDC from the isolating amplifier
- Housing: M12 x 1 chrome-plated brass, PA12-GF30 sensing face, thread length 20 mm, nut torque max. 10 Nm
- Environment: IP67, operating temperature -25...+70 °C
- Connection: 2 m blue PVC cable, 2 x 0.34 mm², Ø 5.2 mm
Suitable for safety-related systems up to SIL 2 (IEC 61508) and PL c (ISO 13849-1) in a single-channel setup. A yellow LED shows the switching state.
ATEX II 1 G Ex ia IIC T6 Ga / II 1 D Ex ia IIIC T135 °C Da (KEMA 02 ATEX 1090X). MTTF 6198 years (SN 29500, 40 °C).