Electromagnetic flow meter PFM43-2211.A1421.0, DN 80...500, pulse output, G 1", L=176mm, M12
Out of stock
2,235.60 €

PFM43-2211.A1421.0 is a Baumer electromagnetic insertion flow meter for pipes from DN 80 to DN 500. It is inserted into the pipe through a G 1 A threaded connection, so a large line does not need a full-bore flow meter. It passes flow velocity on as a pulse or frequency signal, and it is configured with Baumer BCP software.

  • Measuring range: flow velocity 0.4...10 m/s, pipes DN 80...DN 500
  • Accuracy: ±2 % at ≥ 0.5 m/s, repeatability ±0.5 %
  • Output: 2 x pulse/frequency/alarm; analogue 0...20 mA or 4...20 mA output - optional
  • Supply: 10...30 V DC, ≤ 1 W
  • Housing: AISI 316, L=176 mm; G 1 A connection in AISI 304, Hastelloy C electrodes, PEEK and PTFE seals
  • Environment: IP67; process -10...100 °C, up to 100 bar; ambient -10...60 °C
  • Connection: M12-A, 5-pin, stainless steel

The medium must have a conductivity above 20 µS/cm, so the meter is not suitable for demineralised water or oils. After power-up it is operational within 30 s, but calibration needs a warm-up of up to 15 min.

Flow sensors
Electromagnetic flow meter PFM43-2211.A2421.0, DN 80...1000, pulse output, G 1", L=244mm, M12
Out of stock
2,291.10 €

PFM43-2211.A2421.0 is a Baumer electromagnetic insertion flow meter for pipes from DN 80 to DN 1000. It is inserted into the pipe through a G 1 A threaded connection, so a large line does not need a full-bore flow meter. It passes flow velocity on as a pulse or frequency signal, and it is configured with Baumer BCP software.

  • Measuring range: flow velocity 0.4...10 m/s, pipes DN 80...DN 1000
  • Accuracy: ±2 % at ≥ 0.5 m/s, repeatability ±0.5 %
  • Output: 2 x pulse/frequency/alarm; analogue 0...20 mA or 4...20 mA output - optional
  • Supply: 10...30 V DC, ≤ 1 W
  • Housing: AISI 316, L=244 mm; G 1 A connection in AISI 304, Hastelloy C electrodes, PEEK and PTFE seals
  • Environment: IP67; process -10...100 °C, up to 100 bar; ambient -10...60 °C
  • Connection: M12-A, 5-pin, stainless steel

The medium must have a conductivity above 20 µS/cm, so the meter is not suitable for demineralised water or oils. After power-up it is operational within 30 s, but calibration needs a warm-up of up to 15 min.

Flow sensors
Electromagnetic flow meter PFM43-2211.A3421.0, DN 80...2000, pulse output, G 1", L=462mm, M12
Out of stock
2,410.90 €

PFM43-2211.A3421.0 is a Baumer electromagnetic insertion flow meter for pipes from DN 80 to DN 2000. It is inserted into the pipe through a G 1 A threaded connection, so a large line does not need a full-bore flow meter. It passes flow velocity on as a pulse or frequency signal, and it is configured with Baumer BCP software.

  • Measuring range: flow velocity 0.4...10 m/s, pipes DN 80...DN 2000
  • Accuracy: ±2 % at ≥ 0.5 m/s, repeatability ±0.5 %
  • Output: 2 x pulse/frequency/alarm; analogue 0...20 mA or 4...20 mA output - optional
  • Supply: 10...30 V DC, ≤ 1 W
  • Housing: AISI 316, L=462 mm; G 1 A connection in AISI 304, Hastelloy C electrodes, PEEK and PTFE seals
  • Environment: IP67; process -10...100 °C, up to 100 bar; ambient -10...60 °C
  • Connection: M12-A, 5-pin, stainless steel

The medium must have a conductivity above 20 µS/cm, so the meter is not suitable for demineralised water or oils. After power-up it is operational within 30 s, but calibration needs a warm-up of up to 15 min.

Flow sensors
Flow switch, G1, max +140 C, 230 V/ 0.5 A/ 10 W (NO/NC)
Out of stock
320.00 €
The PSF50 flow detector is designed to work with non-sticky and lightly contaminated liquids. This model uses the principle of switching a reed contact by a magnet driven by a vane at its angular deviation from the vertical due to the movement of a fluid flow. This principle does not require any other energy and the signaller does not need a power supply. The model is designed for installation of pipes from 1″ to 3″. Depending on the diameter of the pipe and the length of the vane, which is adjustable in 1″ to 3″ increments, the point of actuation and release of the annunciator is set. The simple and reliable design, as well as the independence of the fluid direction, make the PSF50 widely applicable in standard flow signaling applications.